MIC2000防爆控(kong)(kong)制(zhi)(zhi)(zhi)器(qi)(qi)是一種氣(qi)體濃度監測和泄漏(lou)集中報警(jing)(jing)控(kong)(kong)制(zhi)(zhi)(zhi)器(qi)(qi),電(dian)(dian)(dian)源由市(shi)電(dian)(dian)(dian)電(dian)(dian)(dian)網或蓄(xu)電(dian)(dian)(dian)池(chi)直接(jie)供電(dian)(dian)(dian)。本報警(jing)(jing)控(kong)(kong)制(zhi)(zhi)(zhi)器(qi)(qi)接(jie)收(shou)RS485信號(hao)和4-20mA,暫時(shi)只能接(jie)收(shou)本公(gong)司新款(kuan)在線檢測儀輸(shu)(shu)出的RS485信號(hao),若需要接(jie)入(ru)其他(ta)廠(chang)家的標準RS485信號(hao)請聯(lian)系我公(gong)司進(jin)行確認。一臺氣(qi)體報警(jing)(jing)控(kong)(kong)制(zhi)(zhi)(zhi)器(qi)(qi)可接(jie)入(ru)120路(lu)總線制(zhi)(zhi)(zhi)RS485輸(shu)(shu)出氣(qi)體探測器(qi)(qi)和8路(lu)4-20mA輸(shu)(shu)出氣(qi)體探測器(qi)(qi),更多輸(shu)(shu)入(ru)通(tong)道可訂制(zhi)(zhi)(zhi)。 特點 1、主電(dian)(dian)(dian)源采用市(shi)電(dian)(dian)(dian)AC220V 50Hz(主板工作電(dian)(dian)(dian)壓為24VDC),備(bei)電(dian)(dian)(dian)采用24V蓄(xu)電(dian)(dian)(dian)池(chi),使(shi)用方(fang)(fang)便(bian) 2、控(kong)(kong)制(zhi)(zhi)(zhi)器(qi)(qi)安裝簡單方(fang)(fang)便(bian) 3、內置(zhi)微處理
技術特性
(1)電源:AC220V(內置(zhi)有AC220V轉24VDC開(kai)關電源)或(huo)24V蓄(xu)電池
(2)功耗(hao):小于 15W
(3)測量范圍:與連接的探測器同步
(4)安裝(zhuang)方(fang)式:壁掛式
(5)報警設(she)定(ding):依據在線檢測儀(yi)可(ke)自由設(she)定(ding),一路探(tan)頭可(ke)控制三組繼(ji)電器
(6)輸入信號;RS485/4-20mA
(7)報(bao)警方式:聲光報(bao)警
(8) 輸出(chu)信號(hao):RS485、4-20mA輸出(chu),其中4-20mA輸出(chu)為選配功能。本控制器一共(gong)(gong)設置了四組(zu)(zu)常規觸(chu)點(24VDC/3A、AC220V/1A)和(he)一組(zu)(zu)公共(gong)(gong)觸(chu)點(24VDC/5A、AC220V/1A);可(ke)擴展為9組(zu)(zu)常開/常閉無源(yuan)觸(chu)點輸出(chu)
(9) 溫度:-20~70℃,濕度:0~95%RH
(10)防爆等(deng)級:IICT6
(11)執(zhi)行標準:a、GB 3836.1—2010 《爆(bao)炸性氣體(ti)環(huan)境用電(dian)氣設備(bei) 通(tong)用要求》 b、 GB 3836.2—2010 《爆(bao)炸性氣體(ti)環(huan)境用電(dian)氣設備(bei) 隔爆(bao)型“d”》
(12)外形尺寸:400*400*375MM(L×H×W)
工作原理、結構、尺寸及面板介紹
4.1 控制(zhi)器的工作原理
報警(jing)控(kong)制器(qi)的CPU循環檢測探測器(qi)的工作狀態(tai),當探測器(qi)監測到(dao)環境的氣體(ti)濃度超過報警(jing)設(she)(she)定值時(shi)控(kong)制器(qi)發出(chu)聲(sheng)、光(guang)報警(jing)并根(gen)據(ju)設(she)(she)置輸出(chu)聯動控(kong)制信號。
4.2 控制器的結構
本產品采用壁掛式結(jie)構,先將掛墻結(jie)構件固定在墻上適(shi)當位置,連接好電源線(xian)、信號線(xian)、輸出控(kong)制(zhi)線(xian),再將控(kong)制(zhi)器掛在結(jie)構件上。
4.3 控制器的機箱外形尺寸
機(ji)箱尺寸:400*400*375mm(長*寬*高(gao))。
4.4 控制器(qi)面板介紹
圖(1)控制器面板
(1)工作(zuo)狀(zhuang)態(tai)指示燈:分(fen)為主電(dian)工作(zuo)、備電(dian)工作(zuo),工作(zuo)狀(zhuang)態(tai)。
主電工作燈:紅色,主電源工作時(shi)常亮;
備電工作(zuo)燈(deng):紅色(se),備電源工作(zuo)時常亮;
工(gong)作狀態燈(deng):綠(lv)/黃(huang)色,控制器(qi)正常(chang)工(gong)作時,綠(lv)色燈(deng)閃亮;控制器(qi)出現故障(zhang)時黃(huang)色燈(deng)閃亮;
(2)濃(nong)度報警(jing)(jing)燈:紅色,當監(jian)控環境的氣體濃(nong)度超過報警(jing)(jing)設(she)定值(zhi)時紅色指示燈閃亮(liang)并(bing)伴(ban)隨有聲音報警(jing)(jing);
(3)聯動狀態(tai)指示燈:從1號到4號共(gong)4個指示燈。在“繼(ji)電器輸出設(she)置”功能中(zhong)可指定某個探測器發(fa)生氣體濃(nong)度達到低(di)濃(nong)或高濃(nong)報(bao)警時(shi)發(fa)出某個或多個聯動信(xin)號。
當(dang)某個聯動(dong)信號輸出時(shi)(shi),其相應的指示(shi)燈常亮、聯動(dong)信號輸出,氣體濃(nong)度低(di)于報(bao)警值時(shi)(shi)指示(shi)燈熄(xi)滅、聯動(dong)信號停止輸出。
(4)按(an)鍵說明:顯示屏(ping)下(xia)方共8個按(an)鍵,說明如下(xia):
復位:控制器如果有歷史報警,“濃度報警”狀態燈會一直亮著,此時按“復位”可消除報警狀態
菜單/返回:按此鍵可進入菜單,當進入菜單后,按下此按鍵,可以返回上級菜單,連續按可退出主菜單
確認:當進入控制器(qi)菜單后,按(an)下此按(an)鍵,可以(yi)進行確認操作
消音:當(dang)控(kong)制器(qi)處于(yu)報警狀(zhuang)態時,蜂鳴器(qi)會一直響,按(an)下(xia)此(ci)按(an)鍵可(ke)以消音,再此(ci)按(an)下(xia)可(ke)恢(hui)復聲音
1. 電(dian)源開關(guan)(guan):扭動按鈕控(kong)制儀器的開關(guan)(guan),左(zuo)邊(bian)(分)為關(guan)(guan)機(ji)(ji),右(you)邊(bian)(合)為開機(ji)(ji)。
2. 電(dian)源指(zhi)示燈(deng):電(dian)源指(zhi)示燈(deng)用(yong)于表示控制器(qi)的電(dian)源狀(zhuang)態(tai),亮燈(deng)代(dai)表儀(yi)器(qi)正常工作(zuo)。
3. 復位鍵:清除(chu)歷史報警(jing)狀(zhuang)態(tai)和報警(jing)輸(shu)出,重新獲(huo)取新的報警(jing)信息